mismatching evaporator coil and condenser coil size

When you go to some sites shopping for ac system, you often see some of the recommendations combine condenser, evaporator coil and furnace altogether, and most importantly in each of the combination, the recommended evaporator coil size will be bigger than the condenser unit. For example, a 3.5 ton condenser unit most likely comes with a recommended 4 to 5 ton evaporator coil. This is done on purpose so that the whole system will be very efficient. So the rule of thumb is that the evaporator coil size should be slightly bigger than the size of the condenser unit.

AC compressor spec

Normally on the AC condenser unit, you will see some numbers for LRA and RLA, you should have these for both compressor and fan motor. Here are what they mean: LRA - Lock Rotor Amps.   The current you can expect under starting conditions when you apply full voltage. It occurs instantly during start up. This is normally a lot higher than RLA. For example, 104 vs 19.2 RLA - Rated Load Amps The maximum current a compressor should draw under any operating conditions. Often mistakenly called running or run load amps which leads people to believe, incorrectly, that the compressor should always pull these amps. FLA - Full Load Amps Changed in 1976 to "RLA - Rated Load Amps". 

CFM and AC

Image
AC and heating size chart:       Typically we need about 1 CFM of air flow per square foot of floor area of conditioned space provided that the ceiling height is about 8 feet above the floor, with a typical number of windows and doors and typical building insulation and heat gain or loss. That is 1 sqft x 8ft = 8 cubic feet space needs 1 CFM. You can use this to roughly calculate how much CFM needs for your space. (Tong added) Examples of components for which air velocity (speed through the device) is particularly important are given in the HVAC Air Velocity table below. Typical HVAC System Air Velocity Specifications (速度, 不是CFM) HVAC Component Recommended Air Velocity / Flow Comments Air Ducts - main trunk, typical 700 - 900 fpm Residential Air Ducts - branch, typical 600 - 700 fpm Residential Air Ducts - target 400 fpm Residential Ducts run through conditioned space ...

Blower size vs evaporator size

"To accurately measure the performance of a system or use the charging data accurately, you must measure the amount of air passing across the evaporator coil. The airflow is measured in cubic feet per minute (CFM). 350 to 400 CFM per ton of cooling is required for proper air conditioning system operation. For example, if you are checking a 3 ton system, the air flow required is between 1050 and 1200 CFM." So normally, an entire system will include furnace, evaporator and condenser. " Evaporator and condenser normally match up using tonnage, that part is easy. But what size of furnace should match up with your evaporator? It makes things a bit confusing because the BTU of furnace do not really match up with either evaporator or condenser tonnage. The reason why the size of the furnace is relevant and important is because furnace blower will be shared during both heating and cooling. So after you figured out the right size of AC, it is important to know the required blowe...

TXV and temperatures

The typical TXV comes factory set for 8-12 degrees of evaporator superheat, which in most cases should be fine. What is the correct setting for evaporator superheat? While it is true lower superheat will make the evaporator more efficient, we need to be more concerned with the compressor or total superheat. If we check the superheat on the suction line 6” from the compressor we should normally have at least 20 degrees of total superheat. This will ensure the compressor is not slugging with liquid even when frost is present. The suction line temperature at the compressor should not exceed 65 degrees to ensure proper compressor cooling. The last but most important reading is the discharge line temperature taken 6” from the compressor. This temperature should never exceed 220 degrees, as higher discharge temperatures will lead to compressor failures. Reducing superheat will lower both the compressor suction line and discharge l...

R-22 and R-410a normal temperatur and pressure

On the low side gauge: R-22: 64 - 81 PSIG R-410a: 110 - 136 PSIG On the high side gauge: The range is a lot wider based on seers. The higher seer rating, the lower psig. The lower seer rating, the higher psig. R-22: 100 - 300 R- 410a: 230 - 325 Cannot charge the system by pressure only due to the cooling days. You will definitely have to look at the superheat. Use subcooling to charge system if TXV Use superheat to charge system if Piston The normal subcooling should be between 8 to 12 degrees. If the target subcooling is not available, then you can normally assume that the target subcooling is 10 or 11, and you should shoot for 11. The target superheat should be calculated using this formula: (indoor web bulb temperature x 3 - 80 - outdoor dry bulb temperature) / 2, this will normally give a fairly accurate target superheat, but if the target superheat is posted on the machine or the machine has a superheat target chart, then the chart should be used, the calculation wont be necessary...